Address: 11400 47th St., Suite A Clearwater, Fl. 33762

Protecting Machine Shops from Transient Surge Damage

A practical guide to reducing transient surge damage and lost revenue in machine shops that rely on high-value, microprocessor-based equipment.

The risk of transient surge damage to machine shops is significantly higher than in a typical office because of the high cost and complexity of the microprocessor-based equipment used in these facilities. This guide outlines measures that can help mitigate damage and lost revenue resulting from transient surge events.

Machine shops commonly receive three-phase electrical service, with typical voltages including 277/480Y, 120/208Y, and 120/240 high-leg delta. Internal transformers may be installed to match the supply voltage to particular machines.

Most machine shops have multiple lathes, mills and drills, along with CNC (Computer Numeric Control) machines used to manufacture products for a variety of industries. CNC equipment can be sensitive to both transient surge events and momentary power interruptions.

Protection from Transient Surge Events

The white paper recommends the following measures to help mitigate the risk of transient surge damage in a machine shop.

  • Have an experienced, licensed electrician or engineer review the facility's grounding. The paper notes that additional ground rods installed next to individual machines may conflict with the single-point grounding approach it describes at the electrical service entrance. Have a qualified professional assess the installation against applicable code requirements.
  • Inspect the ground and soil around the electrical service feed. The source notes that persistently damp or wet soil near the service entrance may be a condition worth investigating when evaluating surge exposure.
  • Check each three-phase device to confirm that its control circuits include loss-of-phase protection. This module interrupts power if one or more phases (A, B and/or C) lose power, helping avoid damage to compressors and motors.
  • Install a quality hard-wired surge protector on the load side of the main electrical disconnect, or at the first panel upstream from the electric meter serving the facility.
  • Install additional hard-wired surge protection on panels throughout the facility. The white paper recommends a layered approach to reduce the opportunity for transient surge energy to travel through the building in search of a path to earth ground.
  • Identify the panel supplying outdoor signs and other devices outside the main building. Install an appropriately selected surge protector on each circuit supplying those devices.
  • Plug computer equipment into a quality surge protector. The original white paper cites a typical price range of $50–$75.

Protection from “Blinks”

Electric utilities use automatic resetting circuit breakers, also called reclosers, to reduce the length of power outages caused by events such as lightning strikes, vehicle collisions with poles, or tree limbs contacting lines.

Like a household circuit breaker, a recloser monitors current flow. When it senses an overcurrent or fault, it opens and then attempts to restore power within seconds rather than allowing a longer outage. The white paper explains that a recloser may cycle three times; if it continues to sense a fault, it opens and locks out until utility personnel can inspect the line.

Although reclosers can reduce lengthy power outages, an interruption during a critical CNC operation can cause serious problems. An unexpected blink may snap milling bits or damage or destroy expensive products being manufactured.

Recommendations for Reducing Damage from Momentary Interruptions

  • Keep a log of recloser operations, including the date, time and number of blinks. If blinks occur more than once every few weeks, share the log with the utility to help identify and correct the source.
  • Contact CNC machine manufacturers to ask whether “ride-through” kits are available to reduce the risk of bit or product damage during blinks. The white paper notes that some variable-frequency drives offer optional ride-through kits, such as inductive chokes installed at the drive's power feed.
  • Consider true online (double-conversion) battery backup for critical microprocessor-based loads. Confirm with the equipment manufacturer that maintaining power with a battery backup will not cause other operational issues.
  • Review CNC machine programming options to determine whether a “lift and park” function is available. The source recommends evaluating this option to reduce the chance of a broken milling bit or damaged product during an interruption.
  • Plug CNC-machine components that use 120-volt receptacles into a high-quality surge protector. The white paper cites a typical price range of $75–$100.
  • Verify that each HVAC, refrigeration or cooler compressor has an operational “time delay upon restart” module. Typical delay times are 3–5 minutes after power is restored, allowing refrigerant pressure to decrease before restart.
  • Visually inspect the soil below the electric meter and around the ground rod. The white paper notes that a damp area caused by an air-conditioning drain or leaking water valve may be worth investigating as part of a facility's surge-risk review.

Protecting Equipment and Production

Careful review of critical equipment and installation of appropriate protective devices can help mitigate the risk of transient surge events and momentary power interruptions causing damage.

Because electrical systems, machine configurations and facility conditions vary, grounding, surge protection and equipment-protection decisions should be evaluated by qualified professionals and coordinated with equipment manufacturers where appropriate.

About KENICK, Inc.

KENICK, Inc. has been providing surge protection products and solutions to the electric utility industry since 1989. Its facility includes a research laboratory where surge protection products can be tested against small, medium, large and extreme transient surge events.

Questions?

Please contact Kenick if you have questions about this article or a particular issue you need help with.

Email: Solutions@kenick.com